Navigare online o scaricare Manuale Utente per Hardware Noshok 2100 Series Field Upgradeable Dual Input Process I. NOSHOK 2100 Series Field Upgradeable Dual Input Process Indicator User Manual Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 36
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
1
G
ACCEPTS TWO 4 - 20 mA OR 0 - 10 VDC INPUT SIGNALS
G
PROGRAMMABLE A/D CONVERSION RATE, 5.3 TO 105
READINGS PER SECOND
G
5-DIGIT 0.56" RED SUNLIGHT READABLE DISPLAY
G
VARIABLE INTENSITY DISPLAY
G
LINEARIZATION/SQUARE ROOT EXTRACTION INPUT RANGE
G
PROGRAMMABLE FUNCTION KEYS/USER INPUTS
G
9 DIGIT TOTALIZER (INTEGRATOR) WITH BATCHING
G
OPTIONAL CUSTOM UNITS OVERLAY W/BACKLIGHT
G
FOUR SETPOINT ALARM OUTPUTS (W/OPTION CARD)
G
COMMUNICATION AND BUS CAPABILITIES (W/OPTION CARD)
G
RETRANSMITTED ANALOG OUTPUT (W/OPTION CARD)
G
NEMA 4X/IP65 SEALED FRONT BEZEL
GENERAL DESCRIPTION
The 2100 Dual Process Input Meter offers many features and performance
capabilities to suit a wide range of industrial applications. Available in two
models, AC or DC power, the meter has the capability to accept two, 4 to 20 mA
or 0 to 10 VDC input signals. Each input signal can be independently scaled and
displayed. In addition, a math function can be performed on the two signals, C +
A + B, C - A - B, C + A - B, AB / C, CA / B, or C (1 - A / B). Any of the three
meter values can have Alarms, Comms, and/or a Retransmitted Analog Output
capability by simply adding optional cards. The optional plug-in output cards
allow the opportunity to configure the meter for current applications, while
providing easy upgrades for future needs.
The update rate of the meter is user selectable. This will help in those
applications where a quick response from the meter is of the utmost importance.
The rate can be adjusted from eight selections with a minimum of 5.3
updates/second to a maximum of 105 updates/second.
The meters employ a bright 0.56" (14.2 mm) red sunlight readable LED
display. The intensity of display can be adjusted from dark room applications up
to sunlight readable, making it ideal for viewing in bright light applications.
The meters provide a MAX and MIN reading memory with programmable
capture time. The capture time is used to prevent detection of false max or min
readings which may occur during start-up or unusual process events.
The signal totalizer (integrator) can be used to compute a time-input product.
This can be used to provide a readout of totalized flow, calculate service intervals
of motors or pumps, etc. The totalizer can also accumulate batch operations.
The meter has four setpoint outputs, implemented on Plug-in option cards.
The Plug-in cards provide dual FORM-C relays (5A), quad FORM-A (3A), or
either quad sinking or quad sourcing open collector logic outputs. The setpoint
alarms can be configured to suit a variety of control and alarm requirements.
Communication and Bus Capabilities are also available as option cards. The
standard output is in Modbus Protocol. Any of the following option cards,
RS232, RS485, DeviceNet, or Profibus can be used with the meter. Readout
values and setpoint alarm values can be controlled through the bus.
Additionally, the meters have a feature that allows a remote computer to directly
control the outputs of the meter.
A linear DC output signal is available as an optional Plug-in card. The card
provides either 20 mA or 10 V signals. The output can be scaled independent of
the input range and can track either the input, totalizer, max/min readings, or
math calculation value.
Once the meters have been initially configured, the parameter list may be
locked out from further modification in its entirety or only the setpoint values
can be made accessible.
The meters have been specifically designed for harsh industrial environments.
With NEMA 4X/IP65 sealed bezel and extensive testing of noise effects to CE
requirements, the meter provides a tough yet reliable application solution.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this unit to directly command motors, valves, or other actuators
not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the unit.
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is
2.1" (53.4) H x 5.0" (127) W.
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
CAUTION: Risk of electric shock.
NOSHOK
2100
SERIES
TECHNICAL MANUAL
FIELD UPGRADEABLE DUAL INPUT PROCESS INDICATOR
Vedere la pagina 0
1 2 3 4 5 6 ... 35 36

Sommario

Pagina 1 - TECHNICAL MANUAL

1GACCEPTS TWO 4 - 20 mA OR 0 - 10 VDC INPUT SIGNALSGPROGRAMMABLE A/D CONVERSION RATE, 5.3 TO 105READINGS PER SECONDG5-DIGIT 0.56" RED SUNLIGHT RE

Pagina 2 - ORDERING INFORMATION

10OVERVIEWPROGRAMMING MENU5.0 PROGRAMMING THE METERDISPLAY MODEThe meter normally operates in the Display Mode. In this mode, the meterdisplays can be

Pagina 3 - GENERAL METER SPECIFICATIONS

115.1 MODULE 1 - SIGNAL INPUT PARAMETERSADC CONVERSION RATESelect the ADC conversion rate. The selection does not affect the displayupdate

Pagina 4

12 DISPLAY VALUE FOR SCALING POINT 2* to General Notes on Scaling1. Input Values for scaling points should be confined to the l

Pagina 5 - OPTIONAL PLUG-IN OUTPUT CARDS

13INPUT A ZERO (TARE) DISPLAY The Zero (Tare) Display provides a way to zero the Input A value at variousinput levels, causing fu

Pagina 6 - 2.0 SETTING THE JUMPERS

14RESET MINIMUMWhen activated (momentary action),  flashes and the Minimum readingis set to the present assigned value. The Minimum funct

Pagina 7 - 3.0 WIRING THE METER

15PROGRAM MODE SECURITY CODE*By entering any non-zero value, the prompt   will appear when tryingto access the Program Mode. Access will o

Pagina 8 - 3.2 INPUT SIGNAL WIRING

16MAX CAPTURE DELAY TIMEWhen the Input Display is above the present MAX value for the entereddelay time, the meter will capture that display

Pagina 9 - 3.5 ANALOG OUTPUT WIRING

17 CALCULATION ROUNDING*CALCULATION CONSTANT VALUEThe constant value is used in the Calculation Function formulas to provideoff

Pagina 10 - 5.0 PROGRAMMING THE METER

18TOTALIZER LOW CUT VALUE* to A low cut value disables Totalizer when the Input Display value falls belowthe value programmed

Pagina 11 - IGNAL INPUT PARAMETERS

195.6 MODULE 6 - SETPOINT (ALARM) PARAMETERS ()PARAMETER MENUFLASHrEvYESLAtC2rEv to  sec to  sec1 to 65000-19999 to 99999norOF

Pagina 12 - ARAMETERS ()

2Ordering Information . . . . . . . . . . . . . . . . . . 2General Meter Specifications . . . . . . . . . . . . 3Optional Plug-In Cards . . . . . .

Pagina 13 -  flashes and

20BAUD RATESet the baud rate to match the other serial communications equipment on theserial link. Normally, the baud rate is set to the hi

Pagina 14

21ABBREVIATED PRINTINGSelect  for full print or Command T transmissions (meter address,parameter data and mnemonics) or  for abbreviated

Pagina 15 - ISPLAY ASSIGNMENT AND

22 MODBUS REGISTER TABLEThe below limits are shown as Integers or HEX < > values. Read and write functions can be performed in either Integers o

Pagina 16

23REGISTER ADDRESS 1REGISTER NAMELOW LIMIT 2HIGH LIMIT 2FACTORYSETTING ACCESSCOMMENTSCH A CH B SEE MODULE 1 FOR DESCRIPTION OF PARAMETERSINPUT PARAMET

Pagina 17

241For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers.2An attemp

Pagina 18 -  to 

25REGISTER ADDRESS 1REGISTER NAMELOW LIMIT 2HIGH LIMIT 2FACTORYSETTING ACCESS COMMENTS40406403964038640412404024039240382Transmit DelayOutput LogicOut

Pagina 19

26REGISTER ADDRESS 1REGISTER NAMELOW LIMIT 2HIGH LIMIT 2FACTORYSETTING ACCESS COMMENTS4050640502Total & Calculation ErrorFactory Service Data Regi

Pagina 20

27Register Identification Chart1. Register Names are also used as Register Mnemonics during full transmission.2. The registers associated with the P c

Pagina 21 - SERIAL MODBUS COMMUNICATIONS

28COMMAND RESPONSE TIMEThe meter can only receive data or transmit data at any one time (half-duplexoperation). When sending commands and data to the

Pagina 22 - MODBUS REGISTER TABLE

29COMMUNICATION FORMATData is transferred from the meter through a serial communication channel.In serial communications, the voltage is switched betw

Pagina 23

3GENERAL METER SPECIFICATIONS1. DISPLAY: 5 digit, 0.56" (14.2 mm) variable intensity red sunlight readable(-19999 to 99999)2. POWER: AC Versions:

Pagina 24

305.9 MODULE 9 - FACTORY SERVICE OPERATIONS ()PARAMETER MENUEnter the desired Display Intensity Level (0-15) byusing the arrow keys. The display

Pagina 25

31This page intentionally left blank

Pagina 26 - ) be set to 

32TROUBLESHOOTINGCHECK: Active (lock-out) user inputENTER: Security code requestedPRESS: Reset KEY (If cannot clear contact factory.)ERROR CODE (Err x

Pagina 27 - !() parameter

335-tOt Totalizer (Integrator) Parameters8-Out Analog Output Parameters7-SrL Serial Communication ParametersDISPLAY PARAMETERFACTORYSETTINGUSER SETTIN

Pagina 28 - Timing Diagrams

34PROGRAMMING QUICK OVERVIEW

Pagina 29 -  - ANALOG UPDATE TIME

35This page intentionally left blank

Pagina 30 - PARAMETER MENU

2100TM-08Corporate Headquarters1010 West Bagley RoadBerea, Ohio 44017Ph: 440.243.0888Fax: 440.243.3472E-mail: [email protected]: www.noshok.com

Pagina 31

416. CERTIFICATIONS AND COMPLIANCES:SAFETYType 4X Enclosure rating (Face only), UL50IEC 1010-1, EN 61010-1: Safety requirements for electrical equipme

Pagina 32 - 1-INP Signal Input Parameters

5WARNING: Disconnect all power to the unit beforeinstalling Plug-in cards.Adding Option CardsThe2100series meters can be fitted with up to three optio

Pagina 33

6Installation The 2100 meets NEMA 4X/IP65 requirements for indoor use when properlyinstalled. The unit is intended to be mounted into an enclosed pane

Pagina 34 - PROGRAMMING QUICK OVERVIEW

7WIRING OVERVIEWElectrical connections are made via screw-clamp terminals located on theback of the meter. All conductors should conform to the meter’

Pagina 35

Sinking Logic Terminal 9: Terminal 10-11:}In this logic, the user inputs of the meterare internally pulled up to +5 V with 22K resistance. The input i

Pagina 36 - Corporate Headquarters

9* Display Readout Legends may be locked out in Factory Settings.** Factory setting for the F1, F2, and RST keys is NO mode.RSTF2MF1LPARDSPKEYHold wit