1GACCEPTS TWO 4 - 20 mA OR 0 - 10 VDC INPUT SIGNALSGPROGRAMMABLE A/D CONVERSION RATE, 5.3 TO 105READINGS PER SECONDG5-DIGIT 0.56" RED SUNLIGHT RE
10OVERVIEWPROGRAMMING MENU5.0 PROGRAMMING THE METERDISPLAY MODEThe meter normally operates in the Display Mode. In this mode, the meterdisplays can be
115.1 MODULE 1 - SIGNAL INPUT PARAMETERSADC CONVERSION RATESelect the ADC conversion rate. The selection does not affect the displayupdate
12 DISPLAY VALUE FOR SCALING POINT 2* to General Notes on Scaling1. Input Values for scaling points should be confined to the l
13INPUT A ZERO (TARE) DISPLAY The Zero (Tare) Display provides a way to zero the Input A value at variousinput levels, causing fu
14RESET MINIMUMWhen activated (momentary action), flashes and the Minimum readingis set to the present assigned value. The Minimum funct
15PROGRAM MODE SECURITY CODE*By entering any non-zero value, the prompt will appear when tryingto access the Program Mode. Access will o
16MAX CAPTURE DELAY TIMEWhen the Input Display is above the present MAX value for the entereddelay time, the meter will capture that display
17 CALCULATION ROUNDING*CALCULATION CONSTANT VALUEThe constant value is used in the Calculation Function formulas to provideoff
18TOTALIZER LOW CUT VALUE* to A low cut value disables Totalizer when the Input Display value falls belowthe value programmed
195.6 MODULE 6 - SETPOINT (ALARM) PARAMETERS ()PARAMETER MENUFLASHrEvYESLAtC2rEv to sec to sec1 to 65000-19999 to 99999norOF
2Ordering Information . . . . . . . . . . . . . . . . . . 2General Meter Specifications . . . . . . . . . . . . 3Optional Plug-In Cards . . . . . .
20BAUD RATESet the baud rate to match the other serial communications equipment on theserial link. Normally, the baud rate is set to the hi
21ABBREVIATED PRINTINGSelect for full print or Command T transmissions (meter address,parameter data and mnemonics) or for abbreviated
22 MODBUS REGISTER TABLEThe below limits are shown as Integers or HEX < > values. Read and write functions can be performed in either Integers o
23REGISTER ADDRESS 1REGISTER NAMELOW LIMIT 2HIGH LIMIT 2FACTORYSETTING ACCESSCOMMENTSCH A CH B SEE MODULE 1 FOR DESCRIPTION OF PARAMETERSINPUT PARAMET
241For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers.2An attemp
25REGISTER ADDRESS 1REGISTER NAMELOW LIMIT 2HIGH LIMIT 2FACTORYSETTING ACCESS COMMENTS40406403964038640412404024039240382Transmit DelayOutput LogicOut
26REGISTER ADDRESS 1REGISTER NAMELOW LIMIT 2HIGH LIMIT 2FACTORYSETTING ACCESS COMMENTS4050640502Total & Calculation ErrorFactory Service Data Regi
27Register Identification Chart1. Register Names are also used as Register Mnemonics during full transmission.2. The registers associated with the P c
28COMMAND RESPONSE TIMEThe meter can only receive data or transmit data at any one time (half-duplexoperation). When sending commands and data to the
29COMMUNICATION FORMATData is transferred from the meter through a serial communication channel.In serial communications, the voltage is switched betw
3GENERAL METER SPECIFICATIONS1. DISPLAY: 5 digit, 0.56" (14.2 mm) variable intensity red sunlight readable(-19999 to 99999)2. POWER: AC Versions:
305.9 MODULE 9 - FACTORY SERVICE OPERATIONS ()PARAMETER MENUEnter the desired Display Intensity Level (0-15) byusing the arrow keys. The display
31This page intentionally left blank
32TROUBLESHOOTINGCHECK: Active (lock-out) user inputENTER: Security code requestedPRESS: Reset KEY (If cannot clear contact factory.)ERROR CODE (Err x
335-tOt Totalizer (Integrator) Parameters8-Out Analog Output Parameters7-SrL Serial Communication ParametersDISPLAY PARAMETERFACTORYSETTINGUSER SETTIN
34PROGRAMMING QUICK OVERVIEW
35This page intentionally left blank
2100TM-08Corporate Headquarters1010 West Bagley RoadBerea, Ohio 44017Ph: 440.243.0888Fax: 440.243.3472E-mail: [email protected]: www.noshok.com
416. CERTIFICATIONS AND COMPLIANCES:SAFETYType 4X Enclosure rating (Face only), UL50IEC 1010-1, EN 61010-1: Safety requirements for electrical equipme
5WARNING: Disconnect all power to the unit beforeinstalling Plug-in cards.Adding Option CardsThe2100series meters can be fitted with up to three optio
6Installation The 2100 meets NEMA 4X/IP65 requirements for indoor use when properlyinstalled. The unit is intended to be mounted into an enclosed pane
7WIRING OVERVIEWElectrical connections are made via screw-clamp terminals located on theback of the meter. All conductors should conform to the meter’
Sinking Logic Terminal 9: Terminal 10-11:}In this logic, the user inputs of the meterare internally pulled up to +5 V with 22K resistance. The input i
9* Display Readout Legends may be locked out in Factory Settings.** Factory setting for the F1, F2, and RST keys is NO mode.RSTF2MF1LPARDSPKEYHold wit